Safetyman Eyewash and Deluge Shower Piping and Water Supply

Safetyman's shower and eye wash systems comply with Australian Standard AS4775 and American Standard ANSI Z358.1 2009 

Eye wash and face Wash Fountains:

These should be connected to a potable water supply with piping no less than 20mm NB. The water inlet provided is 1/2" Male B.S.P. If water spillage, during the regular testing of the facility, is a problem, the basin waste should be connected to the drain. Presssure at the fountain, should be no less than 140kPa and no more than 600kPa. Water delivery to the face wash fountain should not be less than 20 l/min at 140kPa and, for an eye wash, not less than 15 l/min at 140kPa.

Deluge Showers:

Similarly, these should be connected to a reliable, potable supply, preferably with piping of 38mm NB. However, as a minimum, over short distances, 25mm or 32mm lines may be considered, providing water delivery of 150 l/min at 140kPa can be achieved. Pressure should be no less than 140kpa and no more than 600kPa.

So that maintenance work can be carried out on this safety equipment, thought should be given to the installation of a lockable valve upstream from the equipment. This valve should be padlocked in the open position so that unauthorized tampering can not occur. Also, line filters or strainers should be considered.

For additional information, please phone, fax or email:

 

Phone

Australia: 1300 781 288

International: +61 2 9502 2300

Fax:

Australia: 1300 761 244

International: +61 2 9502 1045

For further information from Safetyman, please complete the form below and click on the
'Send' button

Full Name:


Email address:


Query or Quotation Request:




 
 
 
Eye wash and emergency shower supply and installation 

2009 © Copyright - All Rights Reserved
 



Site Search

Emergency Shower and Eye Wash Guide
$14.95
Click on image for details
(Ansi z358.1 2004
Updated to 2009 edition)

United States, Canada, United Kingdom and Australia (See Below)
UNITED STATES
• Emergency Eye Wash and Emergency Shower
GUIDE TO ANSI Z358.1 2004 WITH 2009 UPDATE (Click below)
• GUIDE TO ANSI Z358.1 2004 | 2009 COMPLIANCE AND SAFETY AUDIT
• ANSI Z358.1 2004 | 2009 Compliance Requirements
• Workplace Hazard Identification
• Manufacturers of Eye Washes and Emergency Showers
• Location of emergency safety shower and eyewash equipment
• Emergency Shower Drench and Eye Wash Checklists
• Emergency equipment response training.
CANADA
• Canadian Requirements for Emergency Showers and Eye Wash
UNITED KINGDOM
• Control of Substance Hazardous to Health (COSHH)
AUSTRALIA
• Australian Standard AS4775 | Emergency Deluge Systems
SAFETYMAN SYSTEMS AUSTRALIA
• Safetyman Deluge Showers
DELUGE SYSTEMS - EXPOSED OUTDOOR LOCATIONS
• Decontamination Equipment - You must accept the risk !
• Safetyman Emergency Deluge Showers - Exposed Outdoor Locations
• Safetyman Award Winning 'Comfortcool' for hot, exposed locations
• Safetyman DC 165C - Freestanding Combination 'Comfortcool' Deluge System
DELUGE SYSTEMS - INDOORS AND SHADED LOCATIONS
• Safetyman DC 165 Free-Standing, Combination Emergency Deluge System
EYE WASH AND FACE WASH UNITS - INDOORS AND SHADED LOCATIONS
• Safetyman DE 140 - Free-Standing Eye Wash Station
• Safetyman DF 260 Eye Wash and Face Wash unit
LABORATORY MODELS
• Safetyman DL 285 Hand Held, Aerated Eye/Face/Body Wash
INSTALLATION
• Safetyman Eye Wash and Deluge Shower Installation
EMERGENCY SIGNS
• Safetyman Emergency Safety Signs
SAFETYMAN CONTACTS AND DISTRIBUTORS
• Contacts for Safetyman Systems

 

 

 

 In the
United States
and Canada
click here for

Speakman Emergency Showers

and here for
Speakman Eye and Face Wash Stations

In AUSTRALIA

Click here for
Safetyman Shower and Eye Wash equipment