Safetyman Eyewash and Deluge Shower Piping and Water Supply
Safetyman's shower and eye wash systems comply with Australian Standard AS4775
and American Standard ANSI Z358.1 2009
Eye wash and face Wash Fountains:
These should be connected to a potable water supply with piping no less than 20mm NB. The water inlet provided
is 1/2" Male B.S.P. If water spillage, during the regular testing of the facility, is a problem, the basin waste
should be connected to the drain. Presssure at the fountain, should be no less than 140kPa and no more than 600kPa.
Water delivery to the face wash fountain should not be less than 20 l/min at 140kPa and, for an eye wash, not less
than 15 l/min at 140kPa.
Deluge Showers:
Similarly, these should be connected to a reliable, potable supply, preferably with piping of 38mm NB. However,
as a minimum, over short distances, 25mm or 32mm lines may be considered, providing water delivery of 150 l/min at
140kPa can be achieved. Pressure should be no less than 140kpa and no more than 600kPa.
So that maintenance work can be carried out on this safety equipment, thought should be given to the
installation of a lockable valve upstream from the equipment. This valve should be padlocked in the open position
so that unauthorized tampering can not occur. Also, line filters or strainers should be considered.
For additional information, please phone, fax or email:
Phone
Australia: 1300 781
288
International: +61 2 9502 2300
Fax:
Australia: 1300 761 244
International: +61 2 9502 1045
For further information from Safetyman, please complete the form
below and click on the
'Send' button
Eye wash and emergency shower supply and installation
2009 © Copyright - All Rights Reserved
|