Emergency Shower | Eye Wash Guide

Emergency Shower Checklist | Eye Wash Checklist

Emergency Shower Checklist – Eye Wash Checklist

The 15 minute flush tip: Don’t forget to install a floor drain or some other means of fluid disposal that complies with local, state and federal codes. There can be a lot of water to clean up if forgotten.

Consistent activation makes the difference between meeting minimum requirements for installed products, and having emergency equipment that is truly functional and provides the best performance in an emergency.

Eye wash checklist

Emergency Shower Checklist Inspection Tag:

 

It’s a good idea to have an Inspection Tag attached to each emergency fixture noting activation as this log also serves as important documentation upon plant inspection.

Employees must be instructed in the location and receive training in the use of the emergency shower and/or eyewash station.

Current Emergency Shower Checklist Standards:

Current standards (ANSI Z358.1 sections 4.6.2 & 4.6.5) require weekly activation of emergency showers and eyewashes to confi rm proper operation, along with a thorough annual inspection.

While ANSI Z358.1 establishes many additional requirements, the standards identified above are commonly overlooked. Each month, OSHA publishes a recap of noted violations and related fines levied against companies; fi nancial penalties for non-compliance often begin at $100,000 and can exceed $1 million.

Costly Emergency Shower Checklist Errors:

In today’s “lawsuit lottery” business climate, even a rich imagination is no match for jury-based settlements.


ANSI Z358.1 – Emergency Shower Checklist and Eye Wash Checklist –  Frequently Asked Questions:

1. With the recent revisions to the ANSI standard, are existing eyewash, shower, and drench hose stations required to meet the guidelines?

Yes. There is no grandfather clause in the Z358.1 Standard that allows equipment to be exempt. As the standard changes, existing shower equipment needs to be updated.

2. Does OSHA use the ANSI standard?

OSHA requires the employer to provide suitable facilities for quick drenching or fl ushing of the eyes. While OSHA has not formally adopted ANSI Z358.1, they refer employers to the standard as a source of guidance. It is the employer’s responsibility to assess the particular conditions related to the needs of the site to ensure the eye/face wash and shower unit(s) provide suitable protection for employees.

3. Does the annual testing require a full 15-minute flow?

Yes. The importance is to ensure tepid water throughout the full 15 minutes as well as maintaining the pressure and shower patterns.

4. What is the difference between an eye/face wash and just an eyewash?

An eyewash is specifi c to eyes, and the water fl ow rate is designed to hit only the eye surface, while an eye/face wash will cover the eyes and a portion of the face. In addition, an eyewash
has a .4 GPM (1.5 LPM) minimum fl ow rate and an eye/face wash has a 3.0 GPM (11.4 LPM) minimum flow rate.

5. Does the simultaneous requirement for shower activation apply to multiple stations?

Those responsible for the health and safety of the area will determine what the potential is for an accident and how many people could be exposed. Once that number is determined, a system
is designed for that number of showers and eyewashes to run simultaneously. Example: if a facility has ten showers within a specific area and are required to have two running at the same time, then two showers must be designed to simultaneously activate properly.

6. Are there guidelines for placement of eye/face wash stations within a building?

The ANSI standard states that the eye/face wash needs to be 10 seconds away from where an accident could occur and needs to be on the same level with no obstructions. For strong acid or

strong caustic, the emergency equipment should be immediately adjacent to the hazard.

7. Is there a distance conversion?

The current ANSI Standard states that the drench equipment must “be in accessible locations that require no more than 10 seconds to reach.” The appendix of the ANSI Z358.1 Standard clarifi es bystating “that the average person covers a distance of approximately 55 feet (16.8 m) in 10 seconds.”

8.  Learn more at Emergency Shower and Eye Wash Guide.

You should refer to the American National Standard ANSI Z358.1-2014 ” Emergency Eye Wash and Shower Equipment ” for a full list.

Critical Workplace Hazard Identification | Manage the Risks

The full ANSI Z358.1 2014 may be purchased HERE